dc.description© 2004. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Vol. 110, Part 1. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.en
dc.description.abstractCenter-glass thermal analysis programs based on one-dimensional models have proved to be exceptionally useful. Recently efforts have been made to extend the analysis to include venetian blinds. It is convenient to model the venetian blind as a planar, homogeneous layer that is characterized by spatially averaged, or “effective,” optical properties. The blind is then included in a series of planar glazing layers. Thermal resistance values were calculated for a window with two layers of uncoated glass and a venetian blind in an air-filled glazing cavity. Three pane spacings and a wide range of slat angles were examined. The longwave effective properties for the blind were obtained using the analysis presented by Yahoda and Wright in a companion paper. The simulation model was completed with one of two simple models dealing with convective heat transfer in the glazing cavity. Calculated results were compared with earlier guarded heater plate measurements, and the agreement was encouraging in spite of the crude convection models used.en
dc.description.sponsorshipNatural Sciences and Engineering Research Councilen
dc.language.isoenen
dc.publisherAmerican Society of Heating, Refrigerating and Air-Conditioning Engineersen
dc.relation.ispartofseries;AN-04-6-1
dc.subjectFenestrationen
dc.subjectVenetian blinden
dc.subjectBetween-panesen
dc.subjectHeat transferen
dc.subjectSimulationen
dc.titleHeat Transfer Analysis of a Between-Panes Venetian Blind Using Effective Longwave Radiative Propertiesen
dc.typeArticleen
dcterms.bibliographicCitationYahoda, D.S., Wright, J.L., "Heat Transfer Analysis of a Between-Panes Venetian Blind Using Effective Longwave Radiative Properties," ASHRAE Transactions, Vol. 110, Pt. 1., pp. 455-462 (2004)en
uws.contributor.affiliation1Faculty of Engineeringen
uws.contributor.affiliation2Mechanical and Mechatronics Engineeringen
uws.typeOfResourceTexten
uws.peerReviewStatusRevieweden
uws.scholarLevelFacultyen


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record


UWSpace

University of Waterloo Library
200 University Avenue West
Waterloo, Ontario, Canada N2L 3G1
519 888 4883

All items in UWSpace are protected by copyright, with all rights reserved.

DSpace software

Service outages