Show simple item record

dc.contributor.authorMeggers, Forrest
dc.contributor.authorGuo, Hongshan
dc.contributor.authorTeitelbaum, Eric
dc.contributor.authorAschwanden, Gideon
dc.contributor.authorRead, Jake
dc.contributor.authorHouchois, Nicholas
dc.contributor.authorPantelic, Jovan
dc.contributor.authorCalabrò, Emanuele
dc.date.accessioned2017-12-13 16:47:52 (GMT)
dc.date.available2017-12-13 16:47:52 (GMT)
dc.date.issued2017-12-15
dc.identifier.urihttp://dx.doi.org/10.1016/j.enbuild.2017.06.033
dc.identifier.urihttp://hdl.handle.net/10012/12709
dc.description.abstractThe Thermoheliodome is an experimental pavilion that explores cooling without air conditioning. The two research aims were to explore the use of indirect evaporative cooling and the geometric reflection of radiant cooling. For evaporative cooling we utilize a cooling tower outside of the pavilion to indirectly supply water chilled near the wet-bulb temperature. The radiant cooling system is made up of 55 coaxial chilled pipes each located in the central axis of cones with reflective surfaces that spectrally reflect the surface of the pipes and expand their radiant view factor to the occupants inside the pavilion. The specific geometry was digitally fabricated using an industrial robot and hot-wire foam cutter. The mean radiant temperature (MRT) was shown to be significantly decreased using thermal imaging cameras and with a novel scanning MRT sensor. The radiant cooling delivered from the fluid is maximized by reflection and concentration of heat emitted by occupants on the pipes, while the convective cooling of the air is minimized because only the small pipes are cooled and the reflecting surfaces are not, so the convective heat transfer surface area is small. Under typical indoor office conditions the ratio of radiant to convective cooling is slightly greater than one. For the Thermoheliodome the radiant ratio was greater than 10. Occupant surveys found that although the air temperature was not modified, they felt that inside the space there is a cooling sensation (p≤0.01). The day of the survey they felt on average 3°C cooler.en
dc.language.isoenen
dc.publisherElsevieren
dc.rightsAttribution-NonCommercial-NoDerivatives 4.0 International*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/*
dc.subjectRadiant coolingen
dc.subjectDigital fabricationen
dc.subjectEvaporative coolingen
dc.subjectLow exergyen
dc.subjectThermoheliodomeen
dc.titleThe Thermoheliodome – “Air conditioning” without conditioning the air, using radiant cooling and indirect evaporationen
dc.typeArticleen
dcterms.bibliographicCitationMeggers, F., Guo, H., Teitelbaum, E., Aschwanden, G., Read, J., Houchois, N., … Calabrò, E. (2017). The Thermoheliodome – “Air conditioning” without conditioning the air, using radiant cooling and indirect evaporation. Energy and Buildings, 157(Supplement C), 11–19. https://doi.org/10.1016/j.enbuild.2017.06.033en
uws.contributor.affiliation1Faculty of Engineeringen
uws.contributor.affiliation2Architectureen
uws.typeOfResourceTexten
uws.typeOfResourceTexten
uws.peerReviewStatusRevieweden
uws.scholarLevelFacultyen


Files in this item

Thumbnail
Thumbnail

This item appears in the following Collection(s)

Show simple item record

Attribution-NonCommercial-NoDerivatives 4.0 International
Except where otherwise noted, this item's license is described as Attribution-NonCommercial-NoDerivatives 4.0 International

UWSpace

University of Waterloo Library
200 University Avenue West
Waterloo, Ontario, Canada N2L 3G1
519 888 4883

All items in UWSpace are protected by copyright, with all rights reserved.

DSpace software

Service outages