Comparative Technical and Life Cycle Cost Assessment of VSR and STATCOM for Long HVAC Submarine Cables
| dc.contributor.author | Algahtani, Mufarreh | |
| dc.date.accessioned | 2026-08-21T16:35:04Z | |
| dc.date.issued | 2026-08-21 | |
| dc.date.submitted | 2026-08-06 | |
| dc.description.abstract | Long HVAC submarine cables generate significant capacitive charging current, which can cause voltage rise, reactive-power imbalance, and operational limitations when supplying offshore loads. Reactive power compensation is then required to maintain acceptable voltage performance and support reliable offshore power transmission. This thesis compares two compensation technologies for a long offshore HVAC submarine cable system: variable shunt reactors (VSRs) and static synchronous compensators (STATCOMs). The study is based on an developed PSCAD model of a double-circuit offshore transmission system supplying a constant PQ load. Three configurations are evaluated: an uncompensated baseline, a VSR-compensated system, and a STATCOM-compensated system. The technical assessment includes steady-state voltage performance, zero-sequence frequency scan behavior, transient recovery voltage, and response to sudden load loss. The simulation results show that the uncompensated system experiences an unacceptable voltage rise, with the receiving end voltage reaching approximately 1.15 p.u. Both the VSR and STATCOM configurations reduce the voltage profile to within the adopted 0.95–1.05 p.u. operating range under light-load and full-load conditions. The frequency scan results show that compensation technology affects the zero-sequence resonance characteristic, with the STATCOM configuration shifting the dominant impedance peak to a higher frequency than the VSR configuration. The transient recovery voltage results show that both compensation alternatives remain within the specified breaker capability limits for all simulated fault cases. The disturbance response results also show acceptable voltage behavior following sudden load loss. A Life cycle cost assessment is then performed using a 20-year life-cycle cost method. The results show that the VSR alternative has a significantly lower total life-cycle cost than the STATCOM alternative, with estimated values of approximately $51.04 million and $284.16 million, respectively. Although STATCOM provides faster and more flexible reactive-power control, its higher capital cost, higher active losses, and higher operation and maintenance cost make it less economical for the studied case. Therefore, the VSR configuration is identified as the more cost-effective solution for this offshore HVAC submarine-cable application, while the STATCOM remains technically feasible but economically less attractive. | |
| dc.identifier.uri | https://hdl.handle.net/10012/24007 | |
| dc.language.iso | en | |
| dc.pending | false | |
| dc.publisher | University of Waterloo | en |
| dc.title | Comparative Technical and Life Cycle Cost Assessment of VSR and STATCOM for Long HVAC Submarine Cables | |
| dc.type | Master Thesis | |
| uws-etd.degree | Master of Applied Science | |
| uws-etd.degree.department | Electrical and Computer Engineering | |
| uws-etd.degree.discipline | Electrical and Computer Engineering | |
| uws-etd.degree.grantor | University of Waterloo | en |
| uws-etd.embargo.terms | 0 | |
| uws.contributor.advisor | El-Hag, Ayman | |
| uws.contributor.affiliation1 | Faculty of Engineering | |
| uws.peerReviewStatus | Unreviewed | en |
| uws.published.city | Waterloo | en |
| uws.published.country | Canada | en |
| uws.published.province | Ontario | en |
| uws.scholarLevel | Graduate | en |
| uws.typeOfResource | Text | en |